Application
- Horizontal and building backbone cable.
- Support current and future Category 6 and Category 5 enhanced applications, such as:10 Base-T, 100 Base-T, 1000 Base-T (Gigabit Ethernet), FDDI, ATM
Key features and Standards
- General standards: ISO/IEC 11801 2nd edition (2002), EN 50173 2nd edition (2001),ANSI/TIA/EIA 568-B.2 (2002)
Construction & Dimensions
- Construction: shielded 4 twisted pairs
- Conductor: solid bare copper
- Conductor diameter: AWG 23 (0,55 mm)
- Conductor insulation material: Polyolefin
- Diameter over insulation: 1,15 mm
- Cross web: Polyolefin
- Shield: Aluminum/polyester foil
- Drainwire: AWG 26 solid tinned copper
- Jacket material: FRNC compound
- Outer diameter: 7,30 mm
Pair 1 White-Blue/Blue Pair 2 White-Orange/Orange Pair 3 White-Green/Green Pair 4 White-Brown/Brown Colour identification according toIEC 60304
Electrical characteristics (at 20°C) Nominal mutual capacitance at 1 kHz : 50 nF/km Maximum conductor DCR : 91 Ohm/km NVP - Nominal Velocity of Propagation : 0.70 c SKEW – Propagation delay difference (100 MHz) : typical ≤ 15 ns/100m Mean Characteristic Impedance 4-100 MHz1) : 100 ± 5 Ohm
1): According to cable requirements of ISO/IEC 11801 category 6, Sept. 2002.
General and environmental characteristics Temperature range - operation : -20°C - +60°C Temperature range - installation : 0°C - +50°C Minimum bending radius - operation : 29 mm Minimum bending radius - installation : 58 mm Maximum pulling tension : 50 N Flame retardancy : IEC 332-1 Caloric value : 820 kJ/m Weight (approx.) : 51.0 kg/km Maximum operating voltage : 48 V rms Maximum continuous current per conductor (25°C) : 1.4 A
|